Coefficient of performance (COP)

A heat pump moves heat from cold outdoor air or ground into the house. It uses electrical work to do so, but delivers much more heat than the electricity it uses. The ratio of delivered heat to work used is called the coefficient of performance, COP.

COPHP=QHWCOP_{HP} = \frac{Q_H}{W}COP of a heat pump
QH=QC+WQ_H = Q_C + Wenergy balance

Symbols

QHQ_Hheat delivered to the houseJ
QCQ_Cheat taken from the cold sideJ
WWelectrical workJ

Example

The heat pump uses 2 kWh of electricity and takes 6 kWh from the air:

QH=8Q_H = 8 kWh and COP=8/2=4COP = 8/2 = 4.

COP drops when it is cold outside, because the temperature difference becomes larger.