All courses › Building and Structures

Building and Structures: free practice, theory and problems

Before you can design a beam or a floor, you need to know which loads it must carry. In Norway we follow the Eurocodes (NS-EN 1990 and 1991). You split the loads into permanent and variable loads, turn area loads into line loads on the beams, and apply safety factors.

3 parts42 problems9 concepts explainedPractice examFree
Start practising for free →

Contents

  1. Loads and load combinations
  2. Building physics: heat and moisture
  3. Surveying

1. Loads and load combinations

What is it about?

Before you can design a beam or a floor, you need to know which loads it must carry. In Norway we follow the Eurocodes (NS-EN 1990 and 1991). You split the loads into permanent and variable loads, turn area loads into line loads on the beams, and apply safety factors.

In short

q=p⋅c[kN/m]q = p\cdot c \quad [\text{kN/m}]
qd=1.2 G+1.5 Qq_d = 1.2\,G + 1.5\,Q

Which loads act on a building?

Limit states

Eurocode 0 (NS-EN 1990) is based on the limit state method:

Load combinations

Since all variable loads are unlikely to act at full strength simultaneously, they are combined: one leading variable load is taken in full, the others are reduced by combination factors ψ0\psi_0. A typical ULS combination is

1.2 G+1.5 Q1+1.5∑ψ0,i Qi,1.2\,G + 1.5\,Q_1 + 1.5 \sum \psi_{0,i}\, Q_i,

and several combinations with different leading loads must be checked, taking the worst. When self-weight acts favourably (for example against overturning or uplift), a low factor (0.9 or 1.0) is used. In Norway the National Annex sets the factors to use.

Load path

A good structural engineer follows the load path: from the roof and floors via beams and columns or load-bearing walls down to the foundations and the ground. All loads – including horizontal wind loads – need a continuous path to the ground. Horizontal bracing (diaphragms, cross-bracing, cores) is as important as carrying vertical load.

How to solve the problems

  1. Find the area loads in kN/m² (self-weight and imposed load separately).
  2. Multiply by the spacing to get a line load in kN/m.
  3. Combine with the load factors.
  4. Compute the moment and support reactions for the beam.

Example

Floor joists in a house: self-weight 0.5 kN/m², imposed load 2.0 kN/m², spacing 0.6 m and span 4.0 m.

  1. G=0.5⋅0.6=0.3G = 0.5\cdot 0.6 = 0.3 kN/m and Q=2.0⋅0.6=1.2Q = 2.0\cdot 0.6 = 1.2 kN/m.
  2. qd=1.2⋅0.3+1.5⋅1.2=2.16q_d = 1.2\cdot 0.3 + 1.5\cdot 1.2 = 2.16 kN/m.
  3. M=2.16⋅42/8=4.32M = 2.16\cdot 4^2/8 = 4.32 kNm.

Common mistakes

Area load × spacing = line load. Ultimate: 1.2 G + 1.5 Q. Moment: qL²/8.

Concepts in this part

Practise loads and load combinations in the app →

2. Building physics: heat and moisture

What is it about?

A good house keeps the heat in, the moisture out and the electricity bill low. Building physics is about how heat and moisture pass through walls, roofs and windows. The Norwegian building regulations (TEK17) set requirements for how well each part must be insulated.

In short

R=dλ[m2K/W]R = \frac{d}{\lambda} \quad [\text{m}^2\text{K/W}]
U=1Rsi+∑Ri+Rse[W/m2K]U = \frac{1}{R_{si} + \sum R_i + R_{se}} \quad [\text{W/m}^2\text{K}]

Heat transfer

Heat always flows from warm to cold, in three ways: conduction through materials, convection with moving air (including air leaks) and radiation. A material's insulating ability is given by its thermal conductivity λ\lambda (W/mK): mineral wool about 0.035, timber about 0.12, concrete about 2. Insulation works because it traps still air.

U-value

A construction with several layers has thermal resistance R=∑di/λiR = \sum d_i/\lambda_i plus surface resistances inside and outside. The U-value is U=1/RtotU = 1/R_{tot} (W/m²K), and the heat loss is

Φ=U⋅A⋅ΔT.\Phi = U \cdot A \cdot \Delta T.

TEK17 (the Norwegian building regulations) sets energy requirements and minimum values such as external walls U≤0.22U \leq 0.22, roofs U≤0.18U \leq 0.18, floors U≤0.18U \leq 0.18 and windows U≤1.2U \leq 1.2 W/m²K. Windows remain the weakest point in most buildings.

Thermal bridges and airtightness

Moisture

Air can hold more water vapour the warmer it is. Relative humidity (RH) is the ratio of actual to maximum moisture at that temperature. When air cools, RH rises, and at the dew point (100 %) water condenses. Mould can grow at RH above about 75–80 % over time.

Principles of a moisture-safe external wall in a cold climate:

Sources of moisture

Construction moisture (concrete must dry before flooring), precipitation and driving rain, ground moisture (capillary suction – hence capillary-breaking layers under slabs), leaks and indoor moisture from showers, cooking and people. Good ventilation removes moisture and pollutants from inside.

How to solve the problems

  1. Compute R=d/λR = d/\lambda for each layer (thickness in metres).
  2. Add all the resistances, including RsiR_{si} and RseR_{se}.
  3. U=1/RtotU = 1/R_{tot}, and the heat loss is UAΔTU A \Delta T.

Example

A wall has 200 mm of insulation with λ=0.036\lambda = 0.036 W/mK. Ignore the other layers.

  1. R=0.200/0.036≈5.56R = 0.200/0.036 \approx 5.56 m²K/W.
  2. Rtot=0.13+5.56+0.04=5.73R_{tot} = 0.13 + 5.56 + 0.04 = 5.73 m²K/W.
  3. U=1/5.73≈0.175U = 1/5.73 \approx 0.175 W/m²K, which meets the 0.18 requirement.

Common mistakes

R = d/λ add up, U = 1/R_tot. Heat loss = U·A·ΔT. Vapour barrier on the warm side.

Concepts in this part

Practise building physics: heat and moisture in the app →

3. Surveying

What is it about?

Before a road, a building or a tunnel can be built, the terrain must be surveyed and the structure set out in the right place. Surveying is about coordinates, distances, directions and heights.

In short

s=ΔN2+ΔE2s = \sqrt{\Delta N^2 + \Delta E^2}
Δh=back reading−front reading\Delta h = \text{back reading} - \text{front reading}
A=12∣∑(xi yi+1−xi+1 yi)∣A = \tfrac12\left|\sum (x_i\,y_{i+1} - x_{i+1}\,y_i)\right|

Why surveying?

Everything built must be placed correctly: on the right plot, at the right height and with the right shape. Surveying (geomatics) covers measuring what exists (terrain, existing buildings, utilities) and setting out what is to be built (corners, axes, levels). Setting-out errors can be very expensive.

Coordinate systems and heights

Instruments and methods

Angles and direction

Surveyors often use gon (400 gon in a full circle), not degrees. 100 gon = 90°. Bearings are measured clockwise from north.

Errors and checks

All measurements contain errors: gross errors (misreading, wrong point), systematic errors (calibration, temperature) and random errors. That is why measurements are always checked: back to a known point, redundancy (more measurements than needed) and adjustment by least squares. A traverse that starts and ends at known points reveals if something is wrong.

From measurement to model

Measurements feed into BIM and machine control: excavators and pavers with GNSS can work directly from the 3D model, without pegs in the ground.

How to solve the problems

  1. Compute the differences ΔN\Delta N and ΔE\Delta E between the points.
  2. Use Pythagoras for distance, and remember that levelling gives back minus front.
  3. Convert scale by multiplying up and then changing unit.

Example

Point A has a height of 12.345 m. The staff reading at A is 1.200 m and at B 0.800 m.

  1. Δh=1.200−0.800=0.400\Delta h = 1.200 - 0.800 = 0.400 m. Positive, so B is higher.
  2. HB=12.345+0.400=12.745H_B = 12.345 + 0.400 = 12.745 m.

Common mistakes

Distance = √(ΔN² + ΔE²). Levelling: back − front. 400 gon = 360°.

Concepts in this part

Practise surveying in the app →

Example problems with solutions

Here are some of the problems in building and Structures. In the app, calculation problems get new numbers every time, so you can practise until it sticks – and take a practice exam with an indicative grade as you prepare for the exam.

Loads and load combinations: A floor has an imposed load of 2.0 kN/m². The beams are spaced 0.6 m apart. What line load does each beam get from the imposed load?

Answer: 1.2 kN/m

q=p⋅c=2.0⋅0.6=1.2q = p\cdot c = 2.0\cdot 0.6 = 1.2 kN/m.

Building physics: heat and moisture: What is the thermal resistance of 200 mm of insulation with λ=0.036\lambda = 0.036 W/mK?

Answer: 5.556 m²K/W

R=d/λ=0.200/0.036≈5.56R = d/\lambda = 0.200/0.036 \approx 5.56 m²K/W.

Surveying: Point A has the coordinates N = 100, E = 200 and point B N = 130, E = 240 (metres). How far apart are the points?

Answer: 50 m

ΔN=30\Delta N = 30 and ΔE=40\Delta E = 40, so s=302+402=2500=50s = \sqrt{30^2 + 40^2} = \sqrt{2500} = 50 m.

Loads and load combinations: A beam has a permanent load of 3.0 kN/m and an imposed load of 2.0 kN/m. What is the design load in the ultimate limit state (1.2G + 1.5Q)?

Answer: 6.6 kN/m

qd=1.2⋅3.0+1.5⋅2.0=3.6+3.0=6.6q_d = 1.2\cdot 3.0 + 1.5\cdot 2.0 = 3.6 + 3.0 = 6.6 kN/m.

Practise all the problems →